Authorised CITEL distributor · dispatched from Secunderabad

CITEL DS42S-230/G

Type 2 AC surge protector - Single-phase

Type 2 SPD, Single phase, Uc 255 Vac, In 20 kA, Imax 40 kA. CITEL P/N 461531.

₹4,360 per piece, ex-GST

WhatsApp for stock & order Proforma / bank transfer Pay online Datasheet (PDF)

Most buyers WhatsApp the part and quantity first: we confirm stock and dispatch date, and send a GST proforma to pay by bank transfer before dispatch. Paying online here is optional.

Delivery 5–6 weeks from order · minimum order 1 piece · GST tax invoice · pan-India dispatch

Ex-GST · delivered to serviceable PIN codes · remote/ODA freight quoted separately · price valid 30 days

Country of origin: France (CITEL). Exact origin for each part is stated on the product marking and your GST tax invoice.

GST tax invoiceRaised against your GSTIN on every order and emailed to you.
Secure paymentUPI, card and netbanking through Razorpay. Your card details are entered on Razorpay’s form, never on our servers.
Covered if it arrives wrongWrong item: tell us within 7 days. Transit damage or shortage: within 48 hours of delivery.

Vasundhara Performance Solutions Pvt Ltd · incorporated 2016 · CIN U74999TG2016PTC112235 · GSTIN 36AAFCV6218F1ZB · D-U-N-S 860399487 · Udyam MSME registered · authorised CITEL distributor · Shipping · Returns & refunds

CITEL DS42S-230/G surge protection device

Type 2 AC surge protector, single-phase (L+N), 230/400V TT-TN, Uc 255Vac, with remote signalling (S) and N/PE gas tube (/G) (DS40 series); In 20kA, Imax 40kA, MOV+GDT, common/differential mode, pluggable modules (DSM40-230 + DSM40G-600), Isccr 25kA; IEC/EN 61643-11.

Range position: CITEL names the DAC50S-11-275 as the current equivalent of this part. DS40 series, 2-pole 1+1 (/G = TT) with remote signalling.

About the DS42S range

used mainly for primary protection of single and 4- phase networks at the main electrical panel. They provide common-mode or common and differential mode. This SPD is based on high energy varistor equipped with thermal disconnector and failure indicator, to comply with standards. The DS40 surge protectors are designed to be used in a multipolar configuration to protect single-phase, 3-phase or 3-phase+Neutral AC networks.They are sometimes associated with dedicated N/PE surge protector based on gas tube technology.

CITEL lists the DAC50S-11-275 as the newer equivalent of this part.

Specifications

CITEL part number461531
SPD type (IEC 61643)2
Network230/400V
Un — nominal line voltage230 Vac
Uc — max continuous operating voltage255 Vac
In — nominal discharge current20 kA
Imax — max discharge current40 kA
Up — voltage protection levelL/N: 1.25 kV; N/PE: 1.5 kV
Protection modesCommon/Differential mode
ConfigurationSingle phase
Remote signallingOutput on changeover contact
MountingSymmetrical rail 35 mm (EN 60715)
StandardsIEC 61643-11 / EN 61643-11 / UL1449 ed.5
Replacement moduleDSM40-230+DSM40G-600

Specifications as published by CITEL on citel.fr. Confirm against the datasheet for your application.

CITEL datasheet for DS42S-230/G →

See the full CITEL Type 2 SPDs range →  ·  All CITEL parts with prices

Similar CITEL parts

Other parts from the same family (Wind turbine protection), closest in voltage first.

PartWhat it isUcPrice ex-GSTDispatch
DS42S-230Type 2 AC surge protector - Single-phase255 Vac₹3,7502 working days
DS44S-400/GSpecification on request — WhatsApp the part number—₹7,1502 working days