| SPD type (IEC 61643) | 1+2 |
| Network | 230/400 V |
| Un — nominal line voltage | 230 Vac |
| Uc — max continuous operating voltage | 280 Vac |
| In — nominal discharge current | 20 kA |
| Imax — max discharge current | 50 kA |
| Iimp — impulse current (10/350 µs) | 12.5 kA |
| Up — protection level L/N at In | 1.3 kV |
| Up — protection level N/PE at In | 1.5 kV |
| Remote signalling | Changeover contact for disconnection status (the RS option of DS134R-280/G) |
| Configuration | 3-phase + Neutral |
| Format | Plug-in modules |
| Replacement module | DSM130R-280 |
| Mounting | Symmetrical rail 35 mm (EN 60715) |
| Standards | IEC 61643-11 / EN 61643-11 / UL 1449 ed.5 |
Specifications as published by CITEL on citel.fr. Confirm against the datasheet for your application.
CITEL page for the DS134R-280/G family (RS = remote-signalling option) →
See the full CITEL Type 1 SPDs range → · All CITEL parts with prices
Country of origin: France (CITEL). Exact origin for each part is stated on the product marking and your GST tax invoice.